Proface LT4300M - 5.7 Modular HMI + Control" Manual de usuario Pagina 35

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 47
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 34
LT-4201TM/4301TM Installation Guide
35
English
Power Cord Preparation
Before using your power cord:
Verify that the ground wire is the same gauge or heavier than the power wires.
Do not use aluminum wires for the power supply’s power cord.
If the conductor end (individual) wires are not twisted correctly, the end wires may either
short loop to each other or against an electrode. To avoid this, use D25CE/AZ5CE cable
ends.
Use wires that are 0.75 to 2.5 mm
2
(18 to 12 AWG) for the power cord, and twist the wire
ends before attaching the terminals.
The conductor type is solid or stranded wire.
To reduce electromagnetic noise, make the power cord as short as possible.
Power Plug Illustration
Connecting the Power Cord
The table explains how to connect the power plug:
Connection Wire
+24Vdc
-0Vdc
FG Grounded terminal connected to the unit chassis
Step Action
1 Confirm the power cord is not connected to the power supply.
2 Check the rated voltage and remove the "DC24V" sticker on the DC power supply
connector.
3 Remove 10 mm (0.39 in.) of the vinyl membrane off the ends of the power code wires.
4 If using stranded wire, twist the ends. Tinning the ends with solder reduces risk of
fraying and ensures good electrical transfer.
5 Push the Opening button with a small and flat screwdriver to open the desired pin hole.
Vista de pagina 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 46 47

Comentarios a estos manuales

Sin comentarios