PL3000 Series Reference Manual
3-8
The System Monitor property can be used to enable or disable any of these output signals.
Rated Voltage DC12V to 24V
Maximum Load Current 120mA/point
Out Voltage Drop
1.5V or less
(at 100mA load current)
Output Points 2 points
Isolation Method Photocoupler Isolation
Dielectric Strength Voltage 500V or more
External Power Supply DC12V / 100mA
Be sure to operate the unit within its maximum load current. If the maximum load
current exceeds this range, a malfunction or PL damage may occur.
Design your electrical system by adding the load current and voltage values to the
terminal voltage. If load current value used is large, the voltage drop of 1.5V or less
will occur between the terminals.
When connecting an induction load, be sure to connect the above drawing’s
protection diode (*1).
For connection pin location details,
+5V
R
PC357
4.7kΩ
SSTA06
Cable
*
1
DC12V
to
24V
DOUT0(-) # 7
DOUT1(-) # 8
DOUT0(+) pin # 2
DOUT1(+) pin # 3
( Interface Circuit )
Load
SEE
PL3000 Series Hardware Manual “Specifications”
Vista de pagina 68