Chapter 3 Specifications
3-7
Communications Cable Specifications
Wiring the COM Interface Connector
(1) Remove the COM I/F connector from the GP.
(2) Use a flat-blade screwdriver (Size 0.4 x 2.5) to loosen the terminal screws.
(3) Strip the communications cable, and attach it to the terminal connector.
(4) Use a flat-blade screwdriver to tighten the appropriate terminal screws on the terminal connector from
step 3.
(5) Insert the connector into the GP unit’s serial interface.
Communications
Cable Diameter
*1
*1 When inserting two wires into one terminal connec-
tor, the simple wire diameter is 0.08 to 0.5mm
2
(28 -
22 AWG), and the stranded wire diameter is 0.08 to
0.75mm
2
(28 - 20 AWG).
0.14 to 1.5mm
2
(28 - 16 AWG)
Conductor Type Simple or Stranded Wire
*2
*2 If the Conductor’s end (individual) wires are not
twisted correctly, the end wires may either short
against each other, or against an electrode.
Conductor Length
Always ensure that the connector has been removed from the GP unit before wiring
the connector. Failure to do so may result in electric shock.
The torque required to tighten these screws is 0.196Nm (1.735[Lbin]).
7 mm
[0.28 in]
(2)
Use a flat-blade
screwdriver to loosen
the terminal screws.
(4)
Use a flat-blade
screwdriver to tighten
the terminal screws.
(3)
Insert the wire into the
terminal connector.
Terminal Connector