GP-4100 Series Hardware Manual
4-8
Power Cord Specifications
Power Connector Specifications
Connecting the Power Cord
(1) Confirm that the GP unit’s Power Cord is unplugged from the power supply.
(2) Use a flat-blade screwdriver (Size 0.4 x 2.5) to loosen the terminal screws.
(3) Strip the power cord, and attach it to the power connector.
Power Cord Diameter
Simple Wire: 0.75 to 1.5mm
2
Stranded Wire: 0.75 to 1mm
2
(18 - 16 AWG)
Conductor Type Simple or Twisted Wire
Conductor Length
Use copper conductors only.
If the Conductor’s end (individual) wires are not twisted correctly, the end wires may
either short against each other, or against an electrode.
+
24V
-
0V
FG
FG Grounding Terminal connected to
the GP
The power supply connector is MKDS 1/3-3,81 (made by Phoenix Contact).
To avoid an electric shock, prior to connecting the GP unit’s power cord terminals to
the power terminal block, confirm that the GP unit's power supply is completely
turned OFF, via a breaker, or similar unit.
The temperature rating of field installed Conductors:75°C only.
5mm
[0.2 in.]
+
-
FG
GP Rear